26
PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
... 7 Installation
... Electrical connections
Set point signal analog (two-wire technology)
Terminals
Nominal operating range
Limit values
Starting at
Load voltage
Impedance
Digital input DI
Terminals
Supply voltage
Input 'logical 0'
Input 'logical 1'
Input Current
Digital output DO
Terminals
Supply voltage
Switching state logical
Direction of action
+11 / 12
4 to 20 mA
Maximum: 50 mA (overload)
Minimum: 3.6 mA
3.8 mA
9.7 V at 20 mA
485
at 20 mA
+81 / 82
24 V DC (12 to 30 V DC)
0 to 5 V DC
11 to 30 V DC
Maximum 4 mA
+83 / 84
5 to 30 V DC
(Control circuit to DIN 19234/NAMUR)
'0': current > 0.35 mA to < 1.2 mA
'1': Current > 2,1 mA
standard logical '0' or logical '1'
(configurable)
Option modules

Module for analog feedback AO*

Without any signal from the positioner (e.g. 'no power' or
'initializing') the module sets the output to > 20 mA (alarm level).
Terminals
Signal range
4 to 20 mA (split ranges can be parameterized)
Supply voltage, two-wire
technology
Characteristic curve
Deviation

Module for digital feedback SW1, SW2*

Two switches for binary position feedback (position adjustable
within the range of 0 to 100 %, ranges cannot overlap)
Terminals
Supply voltage
Signal current
Direction of action

Module for universal input UAI*

Module for a 4 to 20 mA input for universal use.
The range can be scaled. It is used for advanced valve
diagnostics. For example, an ultrasonic sensor can be connected
to detect a faulty valve seat or a phonometer can be connected
to detect cavitation.
The limit values for detecting up-scaling can be freely selected.
Terminals
Nominal operating range
Load voltage
Impedance
24 V DC (10 to 30 V DC)
rising or falling (configurable)
+41 / 42, +51 / 52
(Control circuit to DIN 19234/NAMUR)
< 1,2 mA: Switching state logical '0'
> 2,1 mA: Switching state logical '1'
standard logical '0' or logical '1' (configurable)
400
+31 / 32
< 1 %
5 to 11 V DC
+21 / 22
4 to 20 mA
8 V at 20 mA
at 20 mA