External Position Sensors - ABB TZIDC Commissioning Instruction

Digital positioner
Hide thumbs Also See for TZIDC:
Table of Contents

Advertisement

26
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E
... 5 Installation

External position sensors

With TZIDC only!
A
1
6
B
1
6
1 TZIDC Control Unit
2 Connection cable
3 TZIDC Remote Sensor
4 Actuator
Figure 2: TZIDC with external position sensors
Note
If the device is being operated on a cylinder, for reasons
associated with linearity you should run automatic adjustment
for rotary actuators (refer to Standard automatic adjustment
on page 46).
2
3
5
4
2
7
5
4
M10904
5 Compressed air supply
6 Set point signal
7 Remote position sensor
A TZIDC Control Unit with TZIDC Remote Sensor*
In this version, the components are supplied in two housings,
which together form one harmonized unit.
The following points should be observed during installation:
Housing 1 (TZIDC Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
Housing 2 (TZIDC Remote Sensor) contains the position
sensor and is mounted on the linear and rotary actuator.
Perform mechanical mounting as described in Mechanical
mounting on page 27.
The electrical connection is performed as described in
Connection on device - TZIDC Control Unit with TZIDC
Remote Sensor on page 40.
Note
To connect the TZIDC Remote Sensor, a cable with the following
specifications needs to be used:
3-wire, cross-section 0.5 to 1.0 mm
shielded, with at least 85 % coverage
Temperature range up to at least 100 °C (212 °F)
The cable glands must also be approved for a temperature range
up to at least 100 °C (212 °F). The cable glands require a
mounting for the shielding and strain relief for the cable in
addition.
ABB optionally offers a cable gland and cable for the
TZIDC Remote Version.
*
The TZIDC Remote Version is temporarily not available for the marine
version.
B TZIDC Control Unit for remote position sensor
In this version the positioner is supplied without a position
sensor.
The following points should be observed during installation:
Housing 1 (TZIDC Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
The remote position sensor is mounted on the linear and
rotary actuator. Follow the operating instructions for the
remote position sensor for mechanical mounting!
The electrical connection is performed as described in
Connection on device - TZIDC Control Unit for remote
position sensor on page 41.
²

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-110Tzidc-120

Table of Contents