126 Technical data

Electrical power network specification

Supply voltage
Network type
Frequency
Imbalance
Short-circuit withstand
strength
(IEC 61439-1)
Short-circuit current
protection (UL 508A,
CSA C22.2 No. 14-13)
Overvoltage category
Power factor
Harmonic distortion
400 V AC units; 380/400/415 V AC 3-phase ± 10%. This is indicated in type
designation label as typical input voltage levels (3~ 400 V AC).
500 V AC units; 380/400/415/440/460/480/500 V AC 3-phase ± 10%. This is
indicated in type designation label as typical input voltage levels
(3~ 400/480/500 V AC).
690 V AC units; 525...690 V AC 3-phase ± 10%. This is indicated in type
designation label as typical input voltage levels (3~ 525/600/690 V AC).
TN (grounded) and IT (ungrounded) systems. 525...600 V AC in corner-
grounded TN systems
50/60 Hz, Variation ± 5% of the nominal frequency
Maximum 3% of nominal phase-to-phase voltage
IEC/EN 61439-1:2009
Frame 1×R8i
Maximum allowable prospective short-circuit current (I
cable must be equipped with fuses as follows:
• maximum 1250 A gG* for frame size R8i
*) Type gG according to IEC 60269
Maximum allowed operating time is <0.1 s for fuses mentioned above.
Frame R8i multiples:
Rated peak withstand current (I
breaker and earthing/grounding switch)
Rated short-time withstand current (I
circuit breaker and earthing/grounding switch)
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when the input cable is
protected with class T fuses.
OVCIII
cosphi 1 = 1, cosphi (total) = 0.99
Harmonics are below the limits defined in IEEE519. Measurements are done
according to IEC 61000-4-7.
R
sc
20
100
2
I
50
 
 
n
I
2
N
THD = Total Harmonic Distortion (THD). The voltage THD depends on the short-
circuit ratio (R
). The spectrum of the distortion also contains interharmonics.
sc
R
= I
/I
sc
sc
N
I
= short-circuit current at point of common coupling (PCC)
sc
I
= IGBT supply unit nominal current
N
*Other loads may influence the THD value.
cc
): 143 kA. (105 kA for units with air circuit
pk
): 65 kA/1 s (50 kA/1 s for units with air
cw
THD Voltage [%]
3
0.8
th
I
n
harmonic component
n
I
nominal current
N
) is 65 kA. The input
THD Current [%]
2.5*
2.5*