Default Control Connections For The Abb Standard Macro; Terminal Sizes - ABB ACS560 Hardware Manual

Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Default control connections for the ABB standard macro

1...10 kohm
Max.
500 ohm
8 )
6)
9)
R3~R8
6)

Terminal sizes

(frames R0...R8): 0.14...1.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
X1
Reference voltage and analog inputs
1
SCR
Signal cable shield (screen)
External frequency reference:
2
AI1
0...10 V
3
AGND
Analog input circuit, common
4
+10V
10 V DC reference voltage
5
AI2
Not configured
6
AGND
Analog input circuit, common
Output frequency, 0...20 mA
7
AO1
Motor current
8
AO2
9
AGND
Analog output circuit common
X2, X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage output +24 VDC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Forward (0) / reverse (1)
15
DI3
Constant frequency sel 110)
16
DI4
Constant frequency sel 2
17
DI5
Ramp 1 (0) / Ramp 2 (1)
18
DI6
Not configured
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
Built-in fieldbus
29
B+
Internal Modbus RTU (EIA-485). See ACS560
standard control program firmware manual
30
A-
(3AXD50000044997 [English]).
31
DGND
(Frame R0~R2)
S100
TERM&BIAS
Termination resistor and bias resistor switch
(Frame R3~R8)
S100
TERM
Termination resistor switch
S200
BIAS
Bias resistor switch
Safety torque off
X4
R0~R2
R3~R8
33
-
OUT1
34
SGND
OUT2
Safety torque off function. Factory connection.
35
OUT1
SGND
Both circuits must be closed for the drive to
start. See
36
IN1
IN1
7)
37
IN2
IN2
X10
24 V AC/DC (frames R6~R8 only)
40
24 V AC/DC- in
24V AC/DC input, for control unit power supply
when external main power is disconnected.
41
24 V AC/DC+ in
X11
Redundant auxiliary voltage output (frames R0~R2 only)
42
+24 V
Aux. voltage output +24 V DC, max. 250 mA
43
DGND
Aux. voltage output common
44
DCOM
Digital input common for all
2
(all terminals)
Electrical installation 81
1) 4)10)
2)
11)
11)
10)
10)
10)
4) 10)
5) 9)
11)
Ready Run
250 V AC / 30 V DC
2 A
11)
Running
250 V AC / 30 V DC
2 A
11)
Fault (-1)
250 V AC / 30 V DC
2 A
Safe torque off
function.
3)
3)