108 Technical data
Drive Type
Nomin-
ACS560
al In
I
1N
A
025A-4
25
033A-4
33
039A-4
39
046A-4
46
062A-4
62
073A-4
73
088A-4
88
106A-4
106
145A-4
145
169A-4
169
206A-4
206
246A-4
246
293A-4
293
1)
Continuous current when its used in Heady duty applications, allows 130% of IHd for 1 minute every 10
minutes at 40 °C.
See definitions and notes in section

Definitions

U
Nominal voltage
N
I
Nominal input current (rms) at 40 °C (104 °F)
1
I
Maximum output current. Available for two seconds at start.
max
I
Nominal output current. Maximum continuous rms output current allowed (no overload).
N
P
Nominal power of the drive. Typical motor power (no overloading). The kilowatt ratings
N
apply to most IEC 4-pole motors. The horsepower ratings apply to most NEMA 4-pole
motors.
I
Maximum current with 110% overload, allowed for one minute every ten minutes
Ld
P
Typical motor power in light-duty use (110% overload)
Ld
I
Maximum current with 150% overload, allowed for one minute every ten minutes
Hd
P
Typical motor power in heavy-duty use (150% overload)
Hd
Max. current
Output ratings
Nominal use
I
I
max
N
A
A
30.6
25
44.3
33
56.9
39
67.9
46
76
62
104
73
122
88
148
106
178
145
247
169
287
206
350
246
418
293
Definitions (page
Output ratings
Heavy-duty use
P
I
(Continu-
N
Hd
ous)
kW
Hp
A
11
15
17
15
20
24.6
18.5
25
31.6
22
30
37.7
30
40
44.6
37
50
61
45
60
72
55
75
87
75
100
105
90
120
145
110
150
169
132
180
206
160
215
246
108).
P
Hd
kW
Hp
7.5
10
11
15
15
20
18.5
25
22
30
30
40
37
50
45
60
55
75
75
100
90
120
110
150
1)
132
180
3AXD10000561047.xls
Frame
size
R2
R3
R3
R3
R4
R4
R5
R5
R6
R7
R7
R8
R8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents