Drive type
Framesize
ACS560
3-phase U
= 400 V (380...480 V)
N
02A6-4
03A3-4
04A0-4
05A6-4
07A2-4
09A4-4
12A6-4
017A-4
025A-4
033A-4
039A-4
046A-4
062A-4
073A-4
088A-4
106A-4
145A-4
169A-4
206A-4
246A-4
293A-4
1)
The cable sizing is based on maximum parallel layout of 6 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001).
For other conditions, size the cables according to local safety regulations, appropriate input voltage and the
load current of the drive. See also
accepted cable sizes of the drive.
2)
Aluminum cables must not be used with frames R0...R4.
3)
In the USA, aluminum cables must not be used.
See also section
Terminal and lead-through data for the power cables (page
See also section .

Alternative power cable types

The recommended and the not allowed power cable types to be used with the drive are
presented below.
Cu cable type
2
mm
R0
3×1.5 + 1.5
R0
3×1.5 + 1.5
R0
3×1.5 + 1.5
R0
3×1.5 + 1.5
R0
3×1.5 + 1.5
R0
3×2.5 + 2.5
R1
3×2.5 + 2.55
R2
3×2.5 + 2.5
R2
3×6 + 6
R3
3×10 + 10
R3
3×10 + 10
R3
3×16 +16
R4
3×25 + 16
R4
3×35 + 16
R5
3×35 + 16
R5
3×50+25
R6
3×95 + 50
R7
3×120 + 70
R7
3×150 + 70
R8
2×(3×70+35)
R8
2×(3×95+50)
Terminal and lead-through data for the power cables (page 117)
Planning the electrical installation 51
1)
IEC
2)
Cu cable type
AI cable type
2
mm
-
-
-
-
-
-
-
-
-
-
-
-
3x35
3x50
3x70
3x70
3×120
3×150
3×240
2×(3×95)
2×(3×120)
US
AI cable type
AWG/kcmil
AWG/kcmil
16
-
16
-
16
-
16
-
16
-
14
-
14
-
14
-
10
-
8
-
8
-
6
-
4
-
2
-
2
-
1/0
-
3/0
-
250 MCM
-
300 MCM
-
2×2/0
-
2×3/0
-
117).
3)
for the

Hide quick links: