B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 34 of 65)
ADDR
REGISTER NAME
7D40
...Repeated for User Programmable Pushbutton 11
7D70
...Repeated for User Programmable Pushbutton 12
7DA0
...Repeated for User Programmable Pushbutton 13
7DD0
...Repeated for User Programmable Pushbutton 14
7E00
...Repeated for User Programmable Pushbutton 15
B
7E30
...Repeated for User Programmable Pushbutton 16
Frequency (Read Only)
8000
Tracking Frequency
Generic Comparator Settings (Read/Write Setting) (6 modules)
8010
Comparator 1 Function
8011
Comparator 1 Addition/Subtraction Mode Operand
8013
Comparator 1 Scale Factor
8014
Comparator 1 Block
8016
Comparator 1 Target
8017
Comparator 1 Events
8018
Comparator 1 Argument A Bits (8 items)
8028
Comparator 1 Input Mode
8029
Comparator 1 Direction Mode
802A
Comparator 1 Pickup
802C
Comparator 1 Hysteresis
802E
Comparator 1 Pickup Delay
802F
Comparator 1 Reset Delay
8030
Comparator 1 Argument B Bits (8 items)
8040
Reserved (4 items)
8044
...Repeated for Comparator 2
8078
...Repeated for Comparator 3
80AC
...Repeated for Comparator 4
80E0
...Repeated for Comparator 5
8114
...Repeated for Comparator 6
Generic Comparator Actual Values (Read Only) (6 modules)
8150
Comparator 1 Argument A Value
8152
Comparator 1 Argument B Value
8154
Comparator 1 Output Value
8156
...Repeated for Comparator 2
815C
...Repeated for Comparator 3
8162
...Repeated for Comparator 4
8168
...Repeated for Comparator 5
816E
...Repeated for Comparator 6
Direct Analog Input Actual Values (Read Only) (32 modules)
8180
Direct Analog Input 1 Value
8182
Direct Analog Input 2 Value
8184
Direct Analog Input 3 Value
8186
Direct Analog Input 4 Value
8188
Direct Analog Input 5 Value
818A
Direct Analog Input 6 Value
818C
Direct Analog Input 7 Value
818E
Direct Analog Input 8 Value
8190
Direct Analog Input 9 Value
8192
Direct Analog Input 10 Value
8194
Direct Analog Input 11 Value
8196
Direct Analog Input 12 Value
8198
Direct Analog Input 13 Value
819A
Direct Analog Input 14 Value
819C
Direct Analog Input 15 Value
B-42
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
2 to 90
Hz
0 to 1
---
0 to 4294967295
---
0.01 to 100
---
0 to 4294967295
---
0 to 2
---
0 to 1
---
0 to 4294967295
---
0 to 1
---
0 to 1
---
-25400 to 25400
---
0 to 5000
---
0 to 65.353
s
0 to 65.353
s
0 to 4294967295
---
0 to 65535
---
-12700 to 12700
---
-12700 to 12700
---
-25400 to 25400
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
APPENDIX B
STEP
FORMAT
DEFAULT
0.01
F001
0
1
F102
0 (Disabled)
1
F300
0
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F300
0
1
F515
0 (SIGNED)
1
F517
0 (OVER)
0.01
F004
1000000
0.01
F003
50000
0.001
F001
0
0.001
F001
0
1
F300
0
1
F001
0
0.01
F004
0
0.01
F004
0
0.01
F004
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
1
F060
0
GE Multilin

Advertisement

Table of Contents
loading