5 SETTINGS
MODIFICATION OF SYNC WORD IN CFG-2 FOR TR 90-5 DATA SETS
In the CFG-2 file, all relevant information about the data being streamed is included. However, this file does not include the
fact that it describes a 90-5 dataset or the number of Application Service Data Units (datasets). In order to communicate
this information via the CFG-2 file for a given aggregator, when the aggregator is set to 90-5, the version number of the
CFG-2 file (found in bits 0-3 of the frame SYNC word - which should presently be set to 2) is set as follows:
VALUE
(DECIMAL)
# OF ASDUS
11
1
12
2
13
3
14
4
The PMU settings are organized in logical groups as follows.

PATH: SETTINGS
SYSTEM SETUP
 PHASOR MEASUREMENT
 UNIT 1
MESSAGE
MESSAGE
MESSAGE
GE Multilin
N60 Network Stability and Synchrophasor Measurement System

PHASOR MEASUREMENT UNIT
 PMU 1 BASIC
 CONFIGURATION
 PMU 1
 CALIBRATION
 PMU 1
 TRIGGERING
 PMU 1
 RECORDING

PHASOR MEASUREMENT UNIT 1(4)
See page 5-112.
See page 5-116.
See page 5-117.
See page 5-125.
5.4 SYSTEM SETUP
5
5-111