APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 65)
ADDR
REGISTER NAME
Phasor Measurement Unit Recorder Config Counter Command (Read/Write Command) (4 modules)
781A
PMU 1 Recorder Clear Config Counter
781B
...Repeated for PMU 2
781C
...Repeated for PMU 3
781D
...Repeated for PMU 4
Phasor Measurement Unit Power Trigger (Read/Write Setting) (4 modules)
7820
PMU 1 Power Trigger Function
7821
PMU 1 Power Trigger Active
7822
PMU 1 Power Trigger Reactive
7823
PMU 1 Power Trigger Apparent
7824
PMU 1 Power Trigger Pickup Time
7825
PMU 1 Power Trigger Dropout Time
7826
PMU 1 Power Trigger Block (3 items)
782C
PMU 1 Power Trigger Target
782D
PMU 1 Power Trigger Events
782E
...Repeated for PMU 2
783C
...Repeated for PMU 3
784A
...Repeated for PMU 4
Phasor Measurement Unit Voltage Trigger (Read/Write Setting) (4 modules)
7858
PMU 1 Voltage Trigger Function
7859
PMU 1 Voltage Trigger Low Voltage
785A
PMU 1 Voltage Trigger High Voltage
785B
PMU 1 Voltage Trigger Pickup Time
785C
PMU 1 Voltage Trigger Dropout Time
785D
PMU 1 Voltage Trigger Block (3 items)
7863
PMU 1 Voltage Trigger Target
7864
PMU 1 Voltage Trigger Events
7865
...Repeated for PMU 2
7872
...Repeated for PMU 3
787F
...Repeated for PMU 4
Phasor Measurement Unit One-shot Command (Read/Write Setting)
788C
PMU One-shot Function
788D
PMU One-shot Sequence Number
788E
PMU One-shot Time
Phasor Measurement Unit Test Values (Read/Write Setting) (4 modules)
7890
PMU 1 Test Function
7891
PMU 1 Phase A Voltage Test Magnitude
7893
PMU 1 Phase A Voltage Test Angle
7894
PMU 1 Phase B Voltage Test Magnitude
7896
PMU 1 Phase B Voltage Test Angle
7897
PMU 1 Phase C Voltage Test Magnitude
7899
PMU 1 Phase C Voltage Test Angle
789A
PMU 1 Auxiliary Voltage Test Magnitude
789C
PMU 1 Auxiliary Voltage Test Angle
789D
PMU 1 Phase A Current Test Magnitude
789F
PMU 1 Phase A Current Test Angle
78A0
PMU 1 Phase B Current Test Magnitude
78A2
PMU 1 Phase B Current Test Angle
78A3
PMU 1 Phase C Current Test Magnitude
78A5
PMU 1 Phase C Current Test Angle
78A6
PMU 1 Ground Current Test Magnitude
78A8
PMU 1 Ground Current Test Angle
78A9
PMU 1 Test Frequency
78AB
PMU 1 Test df/dt
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 1
---
0 to 1
---
0.25 to 3
pu
0.25 to 3
pu
0.25 to 3
pu
0 to 600
s
0 to 600
s
0 to 4294967295
---
0 to 2
---
0 to 1
---
0 to 1
---
0.25 to 1.25
pu
0.75 to 1.75
pu
0 to 600
s
0 to 600
s
0 to 4294967295
---
0 to 2
---
0 to 1
---
0 to 1
---
0 to 99
---
0 to 235959
---
0 to 1
---
0 to 700
kV
-180 to 180
°
0 to 700
kV
-180 to 180
°
0 to 700
kV
-180 to 180
°
0 to 700
kV
-180 to 180
°
0 to 9.999
kA
-180 to 180
°
0 to 9.999
kA
-180 to 180
°
0 to 9.999
kA
-180 to 180
°
0 to 9.999
kA
-180 to 180
°
20 to 70
Hz
-10 to 10
Hz/s
B.4 MEMORY MAPPING
STEP
FORMAT
DEFAULT
1
F126
0 (No)
1
F102
0 (Disabled)
0.001
F001
1250
0.001
F001
1250
0.001
F001
1250
0.01
F001
10
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
0.001
F001
800
0.001
F001
1200
0.01
F001
10
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
1
F001
1
1
F050
0
1
F102
0 (Disabled)
0.01
F003
50000
0.05
F002
0
0.01
F003
50000
0.05
F002
-12000
0.01
F003
50000
0.05
F002
12000
0.01
F003
50000
0.05
F002
0
0.001
F004
1000
0.05
F002
-1000
0.001
F004
1000
0.05
F002
-13000
0.001
F003
1000
0.05
F002
11000
0.001
F004
0
0.05
F002
0
0.001
F003
60000
0.01
F002
0