4.3 FACEPLATE INTERFACE
4 HUMAN INTERFACES
By default, when an incorrect Command or Setting password has been entered via any external communications interface
three times within three minutes, the
FlexLogic™ operand is set to
On
and the N60 does not
REMOTE ACCESS DENIED
"
"
allow settings or command access via the any external communications interface for five minutes. The
REMOTE ACCESS
FlexLogic™ operand is set to "Off" after five minutes for a Command password or 30 minutes for a Settings pass-
DENIED
word.
These default settings can be changed in EnerVista under Settings > Product Setup > Security.