GE N60 Instruction Manual page 155

Ur series network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5 SETTINGS
The
DNP OBJECT 1 DEFAULT VARIATION
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the N60 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The N60 can be configured to sup-
port paired control points, with each paired control point operating two virtual inputs. The
setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on
POINTS
a one-to-one basis.
The
DNP TCP CONNECTION TIMEOUT
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the N60. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the
effect.
NOTE
j) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
PRODUCT SETUP
 DNP / IEC104
 POINT LISTS
MESSAGE
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
 BINARY INPUT / MSP
 POINTS
MESSAGE
MESSAGE
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. Refer to the Introduction to FlexLogic section in this chapter for the full range
of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
to
DNP OBJECT 32 DEFAULT VARIATION
setting specifies a time delay for the detection of dead network TCP connections. If
DNP TCP CONNECTION TIMEOUT


COMMUNICATIONS
DNP / IEC104 POINT LISTS
 BINARY INPUT / MSP
 POINTS
 ANALOG INPUT / MME
 POINTS


COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off
5.2 PRODUCT SETUP
settings allow the user to select the DNP
DNP NUMBER OF PAIRED CONTROL
setting for the changes to take
Range: see sub-menu below
Range: see sub-menu below
BINARY INPUT / MSP POINTS
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
5
5-39

Advertisement

Table of Contents
loading

Table of Contents