2.2 SPECIFICATIONS

2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
NOTE
2
power system devices via communications or different output contacts. If not specified, operate times are given
here for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
PHASE IOC
Pickup level:
Dropout level:
Level accuracy:
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated
> 2.0 × CT rating
Overreach:
Pickup delay:
Reset delay:
Operate time:
Timer accuracy:
SENSITIVE DIRECTIONAL POWER
Measured power:
Number of stages:
Characteristic angle:
Calibration angle:
Minimum power:
Pickup level accuracy:
Hysteresis:
Pickup delay:
Timer accuracy:
Operate time:
PHASE UNDERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
Curve multiplier:
Curve timing accuracy
at <0.90 x pickup:
2-12
0.000 to 30.000 pu in steps of 0.001
97 to 98% of pickup
(whichever is greater)
±1.5% of reading
<2%
0.00 to 600.00 s in steps of 0.01
0.00 to 600.00 s in steps of 0.01
<16 ms at 3 × pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3 × pickup at 60 Hz
(Neutral IOC)
±3% of operate time or ±1/4 cycle
(whichever is greater)
3-phase, true RMS
2
0 to 359° in steps of 1
0.00 to 0.95° in steps of 0.05
–1.200 to 1.200 pu in steps of 0.001
±1% or ±0.001 pu, whichever is greater
2% or 0.001 pu, whichever is greater
0 to 600.00 s in steps of 0.01
±3% of operate time or ±1/4 cycle
(whichever is greater)
<50 ms
0.000 to 3.000 pu in steps of 0.001
102 to 103% of pickup
±0.5% of reading from 10 to 208 V
GE IAV Inverse;
Definite Time (0.1s base curve)
Time dial = 0.00 to 600.00 in steps of
0.01
±3.5% of operate time or ±1/2 cycle
(whichever is greater) from pickup to
operate
N60 Network Stability and Synchrophasor Measurement System
2 PRODUCT DESCRIPTION

2.2.1 PROTECTION ELEMENTS

PHASE OVERVOLTAGE
Voltage:
Phasor only
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0.00 to 600.00 in steps of 0.01 s
Operate time:
<30 ms at 1.10 × pickup at 60 Hz
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
UNDERFREQUENCY
Minimum signal:
0.10 to 1.25 pu in steps of 0.01
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup + 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
OVERFREQUENCY
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup – 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.