GE N60 Instruction Manual page 223

Ur series network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5 SETTINGS
Firmware version 7.0 allows the N60 to support a maximum of four Logical Device PMUs (Logical Device 2 through 5) and
four aggregators (located in Logical Device 1 (LD1)), while other UR family members support one PMU and only one
aggregator. The control blocks for the aggregators are located in LD1. A 64 char LDName setting is provided, see figure
below..
Figure 5–31: N60 SUPPORT FOR FOUR LOGICAL DEVICE PMUS
The specifics of implementation by model number is summarized in the table below.
Table 5–10: IMPLEMENTATION BY MODEL NUMBER
MODEL
NUMBER OF
PMUS
N60
4
D60, F60, G60, L30,
1
L90, T60
Precise time input to the relay from the international time standard, via either IRIG-B or PTP, is vital for correct syn-
chrophasor measurement and reporting. For IRIG-B, a DC level shift IRIG-B receiver must be used for the phasor
measurement unit to output proper synchrophasor values.
NOTE
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
NUMBER OF
NUMBER OF ANALOG
AGGREGATORS
INPUTS
4
16
1
16
5.4 SYSTEM SETUP
COMMENT
1, 2, or 4 PMUs can be used
5
5-107