■Head device
Specify the head device of the consecutive devices. (Page 67 Devices)
The following devices cannot be specified.
• Long timer (contact: LTS, coil: LTC)
• Long retentive timer (contact: LSTS, coil: LSTC)
• Long index register (LZ)
Page 71 Considerations when accessing long timer, long retentive timer, or long counter
Page 71 Considerations when accessing long index register
■Number of device points
Specify the number of device points to be read within the following range. (Page 72 Number of device points)
Access target
MELSEC iQ-R series module
MELSEC-Q/L series module
MELSEC-QnA series module
Module on other station via MELSEC-QnA series network module
MELSEC-A series module
Communication example
Read values of M100 to M107. (Subcommand: for MELSEC-Q/L series)
■Data communication in ASCII code
(Request data)
Subcommand
0
4
0
1
0
0
0
30
34
30
31
30
30
30
H
H
H
H
H
H
H
(Response data)
0
0
0
1
0
0
1
30
30
30
31
30
30
31
H
H
H
H
H
H
H
to
M100
■Data communication in binary code
(Request data)
Device
code
Subcommand
Head device
number
01
04
01
00
64
00
00
H
H
H
H
H
H
H
(Response data)
0 = OFF
1 = ON
00
01
00
11
H
H
H
H
M107
to
M106
M101
M100
Device
Head device number
code
1
M
0
0
0
1
*
31
4D
2A
30
30
30
31
30
H
H
H
H
H
H
H
0 = OFF
1
1 = ON
31
H
M107
Number of
device points
90
08
00
H
H
H
C24
E71
ASCII code
1 to 7904 points
1 to 3584 points
1 to 3952 points
1 to 1792 points
1 to 256 points
Number of device points
0
0
0
0
0
8
30
30
30
30
38
H
H
H
H
H
H
Binary code
1 to 7168 points
1 to 3584 points
8 DEVICE ACCESS