Communication example (for fixed cycle send)
Perform the Programmable controller CPU monitoring registration with the following conditions.
• Cycle time units, cycle time: 30 seconds
• Programmable controller CPU monitoring function: Fixed cycle send
• Number of registered word blocks: 2 blocks
• Number of registered bit blocks: 1 block
• CPU error monitoring: Included
Block
Word device registration (1-point)
Word device registration (2-point)
Bit device registration (1-point)
The response data indicates the following data.
(1) Word device information (1-point)
Device data
Device value
Decimal
Hexadecimal
ASCII code
Word unit
Byte unit
Binary code
Word unit
Byte unit
*1 The additional code is added. (Page 35 Additional code (10H))
(2) Bit device information (1-point)
Device data
Device value
Bit
Byte
Word
ASCII code
Word unit
Byte unit
Binary code
Word unit
Byte unit
(3) CPU status information
• CPU status information: Module warning occurring (0001)
Monitoring start device
D0
W100
M0
D0
D1
99
4144
0063H
1030H
30303633
31303330
36333030
33303130
0063
101030
6300
301010
M15 to M8
M7 to M0
0
0
0
1
0
0
0 1 0 0 1 1 0 0 0 1 0
11H
31H
1131H
31313331
33313131
1131
3111
13 SERIAL COMMUNICATION MODULE DEDICATED COMMANDS
Registered points
4 points
8 points
2 points
D2
5445
1545H
31353435
34353135
*1
1545
*1
4515
M31 to M24
1 0 0 1
48H
4849H
34383439
34393438
4849
4948
13.5 Programmable controller CPU monitoring function
D3
10240
2800H
32383030
30303238
2800
0028
M23 to M16
0
0 0 0
1
0
0
1
0
0
49H
13
1
273