8.2

Batch Read and Write

Read or write the values of consecutive devices in batch by specifying the number of device points.

Batch read in word units (command: 0401)

Read values from devices in word units.
When accessing any of the following devices, use the device extension specification (subcommand: 008).
• Link direct device
• Module access device
• CPU buffer memory access device
For the message format for device extension specification, refer to the following section.
Page 438 Read/Write by Device Extension Specification
Message format
The following shows the message format of the request data and response data of the command.
■Request data
Command
Subcommand
■Response data
The value of read device is stored in word units. The data order differs between ASCII code or binary code. (Page 74
Read data, write data)
When the current value of a long timer or a long retentive timer is read, the values of a contact and a coil are also stored in the
response data. A 4-word response data is read per one device. The configuration of the data to be read is as follows:
Data
1st word
2nd word
3rd word
4th word
Data specified by request data
■Command
Frame
4C/3C/4E/3E frame
2C frame
■Subcommand
Type
For MELSEC-Q/L series
8 DEVICE ACCESS
88
8.2 Batch Read and Write
Number of
Head device
device points
Description
The current value is stored.
b0: The value of the coil is stored.
b1: The value of the contact is stored.
b2 to b15: Used by the system
Used by the system
ASCII code
0
4
0
30
34
30
H
H
H
2
32
H
ASCII code
0
0
0
30
30
30
H
H
H
1
31
H
0
30
H
Binary code
01
04
H
H
Binary code
00
00
H
H