Mitsubishi Electric MELSEC IQ-R series Reference Manual page 419

Programmable controller
Hide thumbs Also See for MELSEC IQ-R series:
Table of Contents

Advertisement

Monitor in word units (command: 09)
Monitor word devices and bit devices (16 point units) which are registered as a monitor data.
■Request data
There is no request data for this command.
■Response data
The value of the read device is stored in word units.
The order of data differs depending on the ASCII code or binary code.
■Communication example
Monitor the devices registered with monitor data registration in the CPU module with E71 mounted under the following
conditions.
• Number of registered device numbers: Y50 to 5F, D38, W1E
(Response data)
(ASCII code)
End code
Subheader
Data for the number of specified device points
8
9
0
0
E
5
6
38
39
30
30
45
35
36
H
H
H
H
H
H
1
1
1
0
0
1
0
(Y5F) to (Y58)
(Binary code)
Subheader
End code
Data for the number of specified device points
89
00
6D
E5
34
12
H
H
H
H
H
(D38)
0
1
1
0
1
1
0
(Y57) to (Y50)
1
2
3
4
5
6
D
44
31
32
33
34
35
36
H
H
H
H
H
H
H
(D38)
1
0
1
1
0
1
1
0
(Y57) to (Y50)
78
56
H
H
H
(W1E)
1
1
1
1
0
0
1
0
(Y5F) to (Y58)
7
8
37
38
H
H
H
(W1E)
1
1
18 COMMUNICATING USING 1E FRAMES
18.4 Read and Write Device Memory
18
417