ABB 800xA Operation page 155

Electrical control system, a safety system and a collaboration enabler
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Section 9 Heat Exchanger Asset Monitor (HXAM)
3BUA000150-600
The text box in
Figure 70
Training and how many BOPS are received out of the expected number during
Monitoring.
Compared Heat Transfer Coefficient:
Value of U: Shows the Ubaseline against which the COPS U is being
compared against during Monitoring. It shows
Calculated Date: Shows the time when the Ubaseline was calculated. It
shows
Not Available
Current Heat Transfer Coefficient:
Value of U: Shows the Unew calculated from the current input data.
Calculated Date: Shows the time when the Unew was calculated.
Condition: Shows the Subcondition of the Heat_Transfer_Performance
condition after assessing the data. It always shows
Training. The different subconditions that will be reported during
Monitoring are as follows:
Normal:
Declining:
Significantly Declining:
Improving:
Significantly Improving:
tells the user how many BOPS are received during
during Training.
Heat Exchanger Heat Transfer
Efficiency is under Normal condition.
Heat Exchanger Heat Transfer
Efficiency has declined. (Unew dropped
by U_Decline_Level from Ubaseline).
Heat Exchanger Heat Transfer
Efficiency has declined significantly.
(Unew dropped by
U_Significant_Decline_Level from
Ubaseline).
Heat Exchanger Heat Transfer
Efficiency has improved. (Unew raised
by U_Improvement_Level from
Ubaseline).
Heat Exchanger Heat Transfer
Efficiency has improved significantly.
(Unew raised by
HXAM_ST_Faceplate
during Training.
-1
during
Normal
155

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents