Commissioning
Summer compensation upper exterior temp. value
Options:
- 9 °C
- 10 °C
- ...
- 32°C
- ...
- 31: 40°C
This specifies the upper outside temperature from which compensation
should be enabled because of a high outside temperature.
Summer compensation lower setpoint offset
Options:
- 0 K
- 1 K
- 2 K
- ...
- 10 K
The "lower setpoint offset" specifies how many K the setpoint should be
increased during summer compensation if the "lower exterior temperature"
is reached.
Typical values for summer compensation are
- 20 °C: lower outside temperature
- 32 °C: upper outside temperature
- 0 K:
lower setpoint offset
- 4 K:
upper setpoint offset
This means that a floating setpoint increase from 0 to 4 K will be
implemented if the outside temperature increases from 20 °C to 32 °C.
Summer compensation upper setpoint offset
Options:
- 0 K
- 1 K
- 2 K
- ...
- 4 K
- ...
- 10 K
The "upper setpoint offset" specifies how many K the setpoint should be
increased during summer compensation if the "upper exterior temperature"
is reached.
Typical values for summer compensation are
- 20 °C: lower outside temperature
- 32 °C: upper outside temperature
- 0 K:
lower setpoint offset
- 4 K:
upper setpoint offset
This means that a floating setpoint increase from 0 to 4 K will be
implemented if the outside temperature increases from 20 °C to 32 °C.