Commissioning
17
Heating setpoint night
mode
Object is visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
setpoint management. When a setpoint for an operating mode is received, the corresponding
setpoint is automatically enabled.
18
Setpoint frost protection
Object is always visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
and relative setpoint management. When a setpoint for an operating mode is received,
the corresponding setpoint is automatically enabled.
19
Cooling setpoint comfort
Object is visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
setpoint management. When a setpoint for an operating mode is received, the corresponding
setpoint is automatically enabled.
20
Cooling setpoint standby
Object is visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
setpoint management. When a setpoint for an operating mode is received, the corresponding
setpoint is automatically enabled.
21
Cooling setpoint night
mode
Object is visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
setpoint management. When a setpoint for an operating mode is received, the corresponding
setpoint is automatically enabled.
22
Setpoint heat protection
Object is always visible if the individual setpoint preset has been set in the parameters.
This data item forms the 2-byte KNX object and can be received. It is relevant for absolute
and relative setpoint management. When a setpoint for an operating mode is received,
the corresponding setpoint is automatically enabled.
Value 99.9 means heat protection = off.
23
Reset of local operation
This 1-bit communication object is enabled, if the proper parameter has been set to "yes".
This object resets the comfort setpoint to the parameterised value.
This data item forms the 1-byte KNX object and can be received only. Manual operation
is reset when a "1" is received.
Control
2 byte
Control
2 byte
Control
2 byte
Control
2 byte
Control
2 byte
Control
2 byte
Control
1 Bit EIS1
DPT 1.001
K, S, Ü,
L
K, S, Ü,
L
K, S, Ü,
L
K, S, Ü,
L
K, S, Ü,
L
K, S, Ü,
L
K, S, Ü,
L