ABB i-bus KNX
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Maximum manual setpoint increase
Options:
- 0 K
- 1 K
- 2 K
- 3 K
- 4 K
- 5 K
- 6 K
- 7 K
- 8 K
- 9 K
- 10 K
If you wish to prevent an excessive temperature increase by the manual
setpoint setting, the upper range of the manual setpoint preset can be
limited with the parameter "Maximum manual setpoint increase".
Example: with a comfort heating temperature of 21 °C and a manual
setpoint adjustment of +/- 3 K, users can select any temperature from 18 °C
to 24 °C. If the comfort temperature can be increased to a maximum of
22 °C, enter "1 K" under the parameter "Max. increase of setpoint".
Maximum manual setpoint reduction
Options:
- 0 K
- 1 K
- 2 K
- 3 K
- 4 K
- 5 K
- 6 K
- 7 K
- 8 K
- 9 K
- 10 K
If you wish to prevent an excessive temperature reduction by the manual
setpoint setting, the lower range of the manual setpoint preset can be
limited with the parameter "Maximum manual setpoint reduction".
Example: with a comfort cooling temperature of 26 °C and a manual setpoint
adjustment of +/- 3 K, users can select any temperature from 23 °C to 29
°C. If the comfort temperature can be reduced to a maximum of 25 °C,
enter "1 K" under the parameter "Max. reduction of setpoint".