Commissioning
Winter compensation active
Options:
- Yes
- No
To improve comfort and to maintain a reasonable temperature differential
when entering a room with a large window area, you should increase
the room temperature depending on the outside temperature in winter
(winter compensation).
This function can only be used together with an external temperature
sensor. If no external temperature sensor is in use, set the parameter
to "No".
CO is shown in the display when compensation is enabled.
Winter compensation lower exterior temp. value
Options:
- -10 °C
- -9 °C
- ...
- 0 °C
- ...
- 21 °C
This specifies the lower outside temperature up to which the setpoint should
be corrected (winter compensation) because of an excessively low outside
temperature.
Winter compensation upper exterior temp. value
Options:
- -10 °C
- -9 °C
- ...
- 10 °C
- ...
- 21 °C
This specifies the upper outside temperature from which the setpoint should
be corrected (winter compensation) because of an excessively low outside
temperature.