15Parameter Window "Fan Coil Cooling - ABB i-bus KNX Product Manual

Room thermostat fan coil with display
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus KNX
3.2.15 Parameter window
"FanCoil cooling"
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Step limit in night mode
Options:
- No limit
- Fan Off
- Stage 1
- Stage 2
If the device is used in an environment such as a hotel room, it may be
desirable to limit the fan stages during the night to reduce the noise.
The parameter "Step limit in night mode" is used for this. If the parameter is
set to stage 1, the fan will not use more that the first stage when night mode
is enabled. This will apply even if the transmitted control value requests a
higher fan stage.
Automatic return from manual adjustment (0 - inactive, min)
Options:
- 0 / 1 / 2 / ... / 60
If "Manual stage switching" was performed by the user, this action can be
reset via onsite operation of the ambient temperature controller. However,
a time can also be input after which the ambient temperature cancels the
"Manual stage switching" and switches back to automatic stage switching
mode.
This parameter is only available if the "Cooling" or "Heat and cool" control
functions are used and the cooling control type is set to "FanCoil".