10Parameter Window "Setpoint General - ABB i-bus KNX Product Manual

Room thermostat fan coil with display
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus KNX
3.2.10 Parameter window
"Setpoint general"
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Setpoint larger when sending change
Options:
- Inactive
- 0.1 K
- 0.2 K
- 0.3 K
- 0.4 K
- 0.5 K
- 0.6 K
- 0.7 K
- 0.8 K
- 0.9 K
- 1.0 K
If this parameter is set to a difference, the associated 2-byte communication
object "Setpoint temperature" sends its current temperature whenever this
parameter changes more than the specified difference.
Cyclic sending of setpoint (0 – inactive, min)
Options:
- 0 / 1 / 2 / ... / 60
If the setpoint is to be sent cyclically independent of a change, the
parameter "Cyclic sending of setpoint" must be set to a time. This may
be necessary, for instance, with a higher-level boiler that expects to receive
setpoints and current values within a certain time period. If values are
not received, a predefined supply line temperature is set that is no longer
oriented on actual demand.
42