ABB i-bus KNX Product Manual page 58

Room thermostat fan coil with display
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus KNX
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Return inactive a fan stage of and automatic return not 0
Options:
- Yes
- No
If the user has manually changed the stage to "switch off", the ambient
temperature controller can also be set so that it does not return to automatic
switching at the end of the "manual switching period" but rather remains
switched off.
This parameter is only available if the "Heating" or "Heat and cool" control
functions are used and the heating control type is set to "FanCoil".
Threshold value stage 1
Options:
- 0%
- 10 %
- ...
- 50 %
- ...
- 100 %
Threshold value stage 1 specifies the magnitude of the control value
required to switch the ambient temperature controller to fan stage 1.
The threshold can be defined in percentages. Make sure that the threshold
for stage 1 is not set higher than the threshold for stage 2 (if available).
This parameter is only available if the "Heating" or "Heat and cool" control
functions are used, the heating control type is set to "FanCoil" and the
number of fan stages is min. "1 stage"..
Threshold value stage 2
Options:
- 0%
- 10 %
- ...
- 40 %
- ...
- 100 %
Threshold value stage 2 specifies the magnitude of the control value
required to switch the ambient temperature controller from fan stage 1 to
fan stage 2. The threshold can be defined in percentages. Make sure that
the threshold for stage 1 is not set higher than the threshold for stage 2
(if available)
This parameter is only available if the "Heating" or "Heat and cool" control
functions are used, the heating control type is set to "FanCoil" and the
number of fan stages is min. "2 stage".
57