ABB i-bus KNX Product Manual page 51

Room thermostat fan coil with display
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus KNX
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Cooling setpoint comfort mode
Options:
- 16.0 °C
- 16.5 °C
- ...
- 23.0 °C
- ...
- 31.0 °C
The "Cooling setpoint comfort mode" specifies the individual comfort
temperature for the cooling mode. This parameter is only available if
the "Cooling" or "Heat and cool" control functions are used, in which the
setpoints "dependent setpoints" (tab "Setpoints general") have been
selected.
Cooling setpoint increase standby
Options:
- 0.5 K
- 1.0 K
- ...
- 2 K
- ...
- 8.0 K
The setting "Cooling setpoint increase standby" allows you to specify
the number of degrees Kelvin that the comfort temperature is increased
during standby operation.
This parameter is only available if the parameter "Selection of base setpoint"
(tab "Setpoint general") is set to "Dependent setpoints".
Cooling setpoint increase night mode
Options:
- 0.5 K
- 1.0 K
- ...
- 4 K
- ...
- 8.0 K
"Cooling setpoint increase night mode" allows you to specify the number of
degrees Kelvin that the comfort temperature is raised during night operation.
This parameter is only available if the parameter "Selection of base setpoint"
(tab "Setpoint general") is set to "Dependent setpoints".
50