Mitsubishi Electric F700 Instruction Manual page 254

Fr-f720-0.75k to 110k; fr-f740-0.75k to 560k
Hide thumbs Also See for F700:
Table of Contents

Advertisement

Causes and corrective actions
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Corrective action
CAUTION
• If protective functions of E.ILF, E.PTC, E.PE2, E.CDO, E.IOH, E.SER, E.AIE are activated when using the FR-PU04, "Fault 14"
appears.
Also when the alarm history is checked on the FR-PU04, the display is "E.14".
• If alarms other than the above appear, contact your sales representative.
246
E.SER
Communication error (inverter)
This function stops the inverter output when communication error occurs consecutively for more than
permissible retry count when a value other than "9999" is set in Pr. 335 RS-485 communication retry count
during RS-485 communication from the RS-485 terminals. This function also stops the inverter output if
communication is broken for the period of time set in Pr. 336 RS-485 communication check time interval.
Check the RS-485 terminal wiring.
Perform wiring of the RS-485 terminals properly.
E.AIE
Analog input error
Appears when 30mA or more is input or a voltage (7.5V or more) is input with the terminal 2/4 set to
current input.
Check the setting of Pr. 73 Analog input selection and Pr. 267 Terminal 4 input selection. (Refer to
143.)
Either give a frequency command by current input or set Pr. 73 Analog input selection or Pr. 267 Terminal
4 input selection to voltage input.
E.13
Internal circuit error
Appears when an internal circuit error occurred.
Please contact your sales representative.
FR-PU04
Fault 14
FR-PU07
VFD Comm error
FR-PU04
Fault 14
FR-PU07
Analog in error
FR-PU04
Fault 13
FR-PU07
page

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents