4.21.4 Current average value monitor signal (Pr. 555 to Pr. 557)

The average value of the output current during
constant speed operation and the maintenance
timer value are output as a pulse to the current
average value monitor signal (Y93).
The pulse width output to the I/O module of the PLC
or the like can be used as a guideline due to
abrasion of machines and elongation of belt and for
aged
deterioration
maintenance time.
The current average value monitor signal (Y93) is
output as pulse for 20s as 1 cycle and repeatedly
output during constant speed operation.
Parameter
Name
Number
555
Current average time
556
Data output mask time
Current average value
557
monitor signal output
reference current
The above parameters can be set when Pr. 160 User group read selection= "0". (Refer to page 156)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write
selection.
1) Data output mask time
When the speed has changed to constant
from acceleration/deceleration, Y93 signal is
not output for Pr.556 time.
2) Start pulse
Output as Hi pulse shape for 1s (fixed)
Time and output current set in Pr.555 are averaged
3) Output current average value pulse
The averaged current value is output as low pulse shape for
0.5 to 9s (10 to 180%) during start bit output.
Signal output time=
⋅ The pulse output of the current average value monitor signal (Y93) is shown above.
⋅ For the terminal used for the Y93 signal output, assign the function by setting "93" (positive logic) or "193" (negative
logic) to any of Pr. 190 to Pr. 194 (output terminal function selection). (The function can not be assigned to Pr. 195 ABC1
terminal function selection and Pr. 196 ABC2 terminal function selection.)
(1) Setting of Pr. 556 Data output mask time
The output current is unstable (transient state) right after the operation is changed from the acceleration/
deceleration state to the constant speed operation. Set the time for not obtaining (mask) transient state data in Pr.
556.
(2) Setting of the Pr. 555 Current average time
The average output current is calculated during Hi output of start bit (1s). Set the time taken to average the current
during start bit output in Pr. 555.
220
of
devices
to
know
Initial
Value
1s
0s
Rated
inverter
current
Y93 signal
output current average value (A)
Pr.557 (A)
maintenance
time
the
parts have
reached their life
Setting Range
0.1 to 1.0s
0.0 to 20.0s
55K or less
75K or more
0 to 3600A
From acceleration to constant speed operation
Output
frequency
1 cycle (20s)
4) Maintenance timer pulse
The maintenance timer value (Pr.503) is output
as Hi output pulse shape for 2 to 9s (16000h to
72000h).
Signal output time=
5s
PLC
Output
Input
unit
unit
Description
Set the time taken to average
the current during start bit
output (1s).
Set the time for not obtaining
(mask) transient state data.
0 to 500A
Set the reference (100%) for
outputting the signal of the
current average value.
Time
Next cycle
5) End pulse
output as low pulse
shape for 1 to 16.5s
Pr.503
100h
5s
40000h
Inverter