Operation Selection At Power Failure And Instantaneous Power Failure; Automatic Restart After Instantaneous Power Failure / Flying Start (Pr. 57, Pr. 58, Pr. 162 To Pr. 165, Pr. 299, Pr. 611) - Mitsubishi Electric F700 Instruction Manual

Fr-f720-0.75k to 110k; fr-f740-0.75k to 560k
Hide thumbs Also See for F700:
Table of Contents

Advertisement

Operation selection at power failure and
instantaneous power failure
4.12 Operation selection at power failure and instantaneous
power failure
Purpose
At instantaneous power failure
occurrence, restart inverter without
stopping motor
When undervoltage or a power
failure occurs, the inverter can be
decelerated to a stop.
4.12.1 Automatic restart after instantaneous power failure / flying start
(Pr. 57, Pr. 58, Pr. 162 to Pr. 165, Pr. 299, Pr. 611)
You can restart the inverter without stopping the motor in the following cases.
⋅ when commercial power supply operation is switched to inverter operation
⋅ when power comes back on after an instantaneous power failure
⋅ when motor is coasting at start
Parameter
Name
Number
Restart coasting
57
time
Restart cushion
58
time
Automatic
restart after
162
instantaneous
power failure
selection
First cushion
163
time for restart
First cushion
164
voltage for
restart
Stall prevention
165
operation level
for restart
Rotation
direction
299
detection
selection at
restarting
Acceleration
611
time at a restart
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 156)
126
Parameter that must be Set
Automatic restart operation
after instantaneous power
failure / flying start
Power failure-time
deceleration-to-stop
function
Initial Value
Setting Range
9999
55K or less
75K or more
1s
0 to 60s
0
0s
0 to 20s
0%
0 to 100%
120%
0 to 150%
9999
55K or less
5s
0 to 3600s, 9999
75K or more
15s
Pr. 57, Pr. 58, Pr. 162 to Pr. 165,
Pr. 299, Pr. 611
Pr. 261 to Pr. 266
1.5K or less....................................0.5s
2.2K to 7.5K...................................1s
0
11K to 55K ....................................3.0s
75K or more...................................5.0s
The above times are coasting time.
0.1 to
5s
Set the waiting time for inverter-triggered restart
after an instantaneous power failure.
0.1 to
30s
9999
No restart
Set a voltage starting time at restart.
0
With frequency search
Without frequency search (Reduced voltage
1
system)
10
Frequency search at every start
11
Reduced voltage system at every start
Set a voltage starting time at restart.
Consider using these parameters according to the
load (moment of inertia, torque) magnitude.
Consider the rated inverter current as 100% and
set the stall prevention operation level during
restart operation.
0
Without rotation direction detection
1
With rotation direction detection
When Pr. 78="0", the rotation direction is detected.
9999
When Pr. 78="1","2", the rotation direction is not
detected.
Set the acceleration time to reach the set
frequency at a restart.
Acceleration time for restart is the normal acceleration
time (e.g. Pr. 7) when "9999" is set.
Refer to Page
126
130
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents