Du/Pu Monitor Display Selection (Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891) - Mitsubishi Electric F700 Instruction Manual

Fr-f720-0.75k to 110k; fr-f740-0.75k to 560k
Hide thumbs Also See for F700:
Table of Contents

Advertisement

Monitor display and monitor output signal
4.11.2 DU/PU monitor display selection
(Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)
The monitor to be displayed on the main screen of the operation panel (FR-DU07)/parameter unit (FR-PU04/FR-
PU07) can be selected.
Parameter
Name
Number
DU/PU main display data
52
selection
FM terminal function
54
selection
AM terminal function
158
selection
170
Watt-hour meter clear
171
Operation hour meter clear
Monitor decimal digits
268 *
selection
Energization time
563
carrying-over times
Operating time carrying-
564
over times
Cumulative power monitor
891
digit shifted times
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 156)
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection.
(1) Monitor description list (Pr. 52)
⋅ Set the monitor to be displayed on the operation panel (FR-DU07) and parameter unit (FR-PU04/FR-PU07) in Pr.
52 DU/PU main display data selection.
⋅ Set the monitor to be output to the terminal FM(pulse train output) in Pr. 54 FM terminal function selection.
⋅ Set the monitor to be output to the terminal AM (analog output (0 to 10VDC voltage output)) in Pr. 158 AM terminal
function selection.
⋅ Refer to the following table and set the monitor to be displayed. (The signals marked × cannot be selected for
monitoring)
Types of Monitor
Increments
Output frequency
0.01Hz
0.01A/0.1A
Output current
Output voltage
0.1V
Alarm display
Frequency setting
0.01Hz
Running speed
1(r/min)
116
Initial Value
0
(output
frequency)
1
(output
frequency)
9999
9999
9999
0
0
9999
Pr. 52 Parameter
Setting Value
PU main
DU LED
monitor
0/100
0/100
*5
0/100
0/100
5
*1
6
*1
Setting Range
0, 5, 6, 8 to 14,
Select the monitor to be displayed on the
17, 20, 23 to 25,
operation panel and parameter unit.
50 to 57, 100
Refer to the following table for monitor description.
Select the monitor output to terminal FM.
1 to 3, 5, 6, 8 to
14, 17, 21, 24,
50, 52, 53
Select the monitor output to terminal AM.
0
Set "0" to clear the watt-hour meter monitor.
Set the maximum value when monitoring from
10
communication to 0 to 9999kWh.
Set the maximum value when monitoring from
9999
communication to 0 to 65535kWh.
Set "0" in the parameter to clear the watt-hour
0, 9999
monitor.
Setting "9999" has no effect.
0
Displayed as integral value.
1
Displayed in 0.1 increments.
9999
No function
The numbers of cumulative energization time
0 to 65535
monitor exceeded 65535h is displayed. Reading
(reading only)
only
0 to 65535
The numbers of operation time monitor
(reading only)
exceeded 65535h is displayed. Reading only
Set the number of times to shift the cumulative
0 to 4
power monitor digit.
Clamp the monitoring value at maximum.
No shift
9999
Clear the monitor value when it exceeds the
maximum value.
Pr. 54 (FM)
Full-scale
Pr. 158 (AM)
value of the
Parameter
terminal FM
Setting
and AM
Value
1
Pr. 55
2
Pr. 56
3
400V
×
5
Pr. 55
The value
converted
6
with the Pr.
37 value
from Pr. 55
Description
Description
Displays the inverter output frequency.
Displays the inverter output current effective
value.
Displays the inverter output voltage.
Displays 8 past alarms individually.
Displays the set frequency.
Displays the motor speed. (depending on Pr.
37 and Pr. 144 settings. (For details, refer to page
115 .)