Special operation and frequency control
Parameter
Name
Number
Output interruption
575
detection time
Output interruption
576
detection level
Output interruption
577
cancel level
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 156)
*1
Pr. 129, Pr. 130, Pr. 133 and Pr. 134 can be set during operation. They can also be set independently of the operation mode.
(1) PID control basic configuration
⋅ Pr. 128 = "10, 11" (Deviation value signal input)
Set point
⋅ Pr. 128 = "20, 21" (Measured value input)
Pr. 133 or
terminal 2
0 to 5VDC
(0 to 10V, 4 to 20mA)
202
Initial
Setting Range
Value
1s
0Hz
1000%
900 to 1100%
Deviation signal
+ -
Terminal 1
0 to
10VDC
(0 to
5V)
To outside
Feedback signal (measured value)
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
Inverter circuit
+ -
Set point
Terminal 4
Feedback signal (measured value)
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
The inverter stops operation if the output frequency after
0 to 3600s
PID operation remains at less than the Pr. 576 setting for
longer than the time set in Pr. 575.
9999
Without output interruption function
Set the frequency at which the output interruption
0 to 400Hz
processing is performed.
Set the level (Pr. 577 minus 1000%) to release the PID
output interruption function.
Inverter circuit
PID operation
1
1+
+Td S
Kp
Ti S
PID operation
1
Kp 1+
+Td
S
Ti
S
4 to 20mADC (0 to 5V, 0 to 10V)
Description
Motor
Manipulated
variable
IM
Motor
Manipulated
variable
IM