Main circuit terminal specifications

2.2 Main circuit terminal specifications

2.2.1

Specification of main circuit terminal

Terminal
Terminal Name
Symbol
R/L1,
S/L2,
AC power input
T/L3
U, V, W
Inverter output
R1/L11,
Power supply for
S1/L21
control circuit
Brake unit
P/+, N/-
connection
DC reactor
P/+, P1
connection
PR, PX
Please do not remove or use terminals PR and PX or the jumper connected.
Earth (ground)
2.2.2
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
200V class
FR-F720-0.75K, 1.5K
Screw size (M4)
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
N/-
Power supply
16
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter
(FR-HC, MT-HC) or power regeneration common converter (FR-CV).
Connect a three-phase squirrel-cage motor.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
alarm display and alarm output or when using the high power factor
converter (FR-HC, MT-HC) or power regeneration common converter (FR-
CV), remove the jumpers from terminals R/L1-R1/L11 and S/L2-S1/L21
and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1/L11, S1/L21) with the
main circuit power (R/L1, S/L2, T/L3) on. Doing so may damage the
inverter. The circuit should be configured so that the main circuit power (R/
L1, S/L2, T/L3) is also turned off when the power supply for control circuit
(R1/L11, S1/L21) is off.
200V class
400V class
Connect the brake unit (FR-BU, BU and MT-BU5), power regeneration
common converter (FR-CV), high power factor converter (FR-HC and
MT-HC) or power regeneration converter (MT-RC).
For the 55K or less, remove the jumper across terminals P/+ - P1 and
connect the DC reactor. (Be sure to connect the DC reactor supplied
with the 75K or more.)
For earthing (grounding) the inverter chassis. Must be earthed
(grounded).
Jumper
PR
P/+
PX
IM
Screw size
(M4)
Motor
Charge lamp
As this is an inside cover fixing screw,
do not remove it.
Description
15K or less
18.5K
60VA
80VA
60VA
60VA
FR-F720-2.2K to 5.5K
Screw size (M4)
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
IM
Power
Motor
supply
22K or more
80VA
80VA
Jumper
PR
P/+
N/-
PX
Screw size
Charge lamp
(M4)