Honeywell enCore Series Manual page 130

Gas quality analyzer
Hide thumbs Also See for enCore Series:
Table of Contents

Advertisement

7
Synchronizing system time
For a user who is not logged in or a user who is logged in but is not entitled to
change the device time, " Time Service – Time Synchronization" will open as the
second display after "Date & Time" has been activated. (System > Time Service >
Date & Time)
Fig. 7-22: Time Service – Time Synchronization display
The display shows following information:
Time synchronization by: A change in the system time is regarded as syn-
l
chronization if the difference between the old and the new system time does
not exceed the parameterized time window (Max. synchronization range).
Enter the seconds in the box by which the system time is to be changed. Both
positive and negative values may be entered. The box will only accept values
within the parameterized synchronization window .
Next possible synchronization: Next possible time for another synchronization.
l
The calculation is made after a synchronization based on the synchronization
interval. The parameter Synchronization Interval determines the time interval
that has to pass after an executed synchronization before the next syn-
chronization can be done. If the entry is Now, you can synchronize the system
time; otherwise, you must wait until the next specified time.
Expected new time: The time service continuously calculates the new system
l
time in this line. You can easily synchronize the system time by specifying the
difference in seconds relative to the current system time.
Synchronize
now: This action (if available) specifically saves the new time as
l
the system time. The action can only be executed if a synchronization is
possible, that is, the specified difference is greater than zero (0) and the
system time has not yet been synchronized within this synchronization in-
terval.
By default, you can synchronize the system time by ± 20 seconds
every 12 hours without having the access right Update device time.
Refer to
➪  
line Help (branch Basic System – Time Service) for information about
the time service parameter setting.
GasLab Q2
8 Configuration and analysis software enSuite
User Manual (N )
GasLab Q2 operation panel and operation
(p.  171)
on-
130 of 315

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gaslab q2

Table of Contents