FDAP Gen3 and FDAP Gen3 Anchor
FDAP2
Mount the FDAP
FDAP Gen3 and FDAP Gen3 Anchor
See the following figure for grounding points for FDAP Gen3 and FDAP Gen3 Anchor.
Grounding points for FDAP Gen3 and FDAP Gen3 Anchor
Fig. 7.
Use one of the two grounding points marked in the image for grounding. Fasten the
screws and washers with a torque value of 12 to 14 inch-pounds (in-lb).
See the following figure for grounding points for FDAP2.
Grounding points for FDAP 1/FADP2
Fig. 8.
The assembled FDAP Gen3 and FDAP Gen3 Anchor, along with antennas and lightning
suppressors (if required) can be mounted in the site location. The FDAP Gen3 and FDAP
Gen3 Anchor enclosure can be mounted on a 2-inch pole or on a wall using the
appropriate optional mounting kit that is available with the unit.