Outputs And Leds Configuration (Only For Option 1 And Option 2 Models); Description Of Outputs And Leds - GE GEK-106273L Instruction Manual

Digital feeder protection
Table of Contents

Advertisement

6.2
OUTPUTS AND LEDS CONFIGURATION (ONLY FOR OPTION 1 AND OPTION 2
MODELS)
The MIF incorporates 4 configurable outputs and 4 LED indicators, which can only be configured by ENERVISTA MII
SETUP software.
The default configuration for outputs is as follows:
OUTPUT
The default LED configuration is as follows:
LED
Functions that can be assigned to Outputs/LEDs are divided in eight groups, besides the No definition function.
Functions belonging to the same group can be assigned to the same output/LED. Functions of different groups need
to be assigned to different outputs/LEDs.
In order to assign several functions to an output/LED, first we must activate the OR button, click on the I/O
CONFIGURATION frame and select the desired group, then select the desired functions. In order to negate a
function, select the NOT button. Finally, click on the OK button.
Now you can invert all the logic by selecting the general NOT button. Outputs can be memorised, and LEDs can be
set to be fixed or blinking.
If we want to assign a phase trip to an output or LED, we must program the output or LED with 50PH pickup, 50PL
pickup and 51P functions.
50PH trip
50PL trip
51P trip
If we want an output or LED to be active when function is Remote, we must program the output or LED with the
Local/Remote function inverted with NOT.
Local/Remo
GEK-106273L
PRODUCT DESCRIPTION
1
2
3
4
1
2
3
4
MIF Digital Feeder Protection
6.2.1.
CONFIGURATION
Phase trip
Ground trip
50 Trip
49 Alarm
CONFIGURATION
Phase trip
Ground trip
50 Trip
Pickup

DESCRIPTION OF OUTPUTS AND LEDS

MEMORY
No
No
No
No
MEMORY
Yes
Yes
Yes
No
Output/LE
Output/L
6-41