Module Withdrawal / Insertion; Wiring And Internal Connections - GE GEK-106273L Instruction Manual

Digital feeder protection
Table of Contents

Advertisement

PRODUCT DESCRIPTION
3.1.3.

MODULE WITHDRAWAL / INSERTION

WARNING: MODULE WITHDRAWAL AND INSERTION SHALL ONLY BE PERFORMED
BY DULY QUALIFIED SERVICE PERSONEL WHEN CONTROL POWER HAS BEEN REMOVED FROM THE
UNIT
The modular design of the relay allows for the withdrawal and insertion of the module.
Figure 3-3: MIF WITHDRAWAL / INSERTION
WITHDRAWAL: Remove the methacrylate cover on the faceplate, loosing the four screws located on the four
corners of the cover. Then loose the small screws that keep the faceplate in place and pull from the knobs located
on the upper and lower side of the faceplate. Before performing this action control power must be removed from
the relay. Current inputs are automatically shorted back in the terminal block when the module is withdrawn.
INSERTION: Proceed inversely to the withdrawal procedure. Press the module firmly in the case, using the knobs,
until it is completely inserted. Once this is done, bolt the screws of the faceplate and replace the control power.
Check if the relay is fully operative. Finally, replace the methacrylate cover.
3.1.4.

WIRING AND INTERNAL CONNECTIONS

The electrical connection with the substation AC/DC wires is done on the three terminal blocks, at the rear part of the
relay case. Each terminal block has 12 terminals (M3, 3 mm diameter).
Current inputs are also located on one of the three terminal blocks, at the rear. This terminal block is designed to
withstand the secondary currents of the substation CTs. The internal wires taking the currents are of greater section
than the rest of the internal wires for the relay inputs. They have been designed to have the shortest length possible,
to minimise the burden in the primary CTs. Internal connections are done through pressing terminals. The internal
current wires are separated from the rest, to minimise the magnetic coupling (associated to high input currents) on
other internal wires carrying weaker signals.