Model List. Order Codes - GE GEK-106273L Instruction Manual

Digital feeder protection
Table of Contents

Advertisement

2.12

MODEL LIST. ORDER CODES

The MIF has a draw-out construction, 4U high and ¼ of a 19" rack wide. The MIF relays can be mounted in ¼ rack
cases, one relay per case, or as an alternative they can be supplied in half or full 19'' rack cases, including several
MIF relays (or different types of M family relays) in the same case. Each M product is built as a stand alone draw-
out module containing all functionally required elements such as CT/VTs, I/O, power supply, CPU etc. MIF, MIM,
MIG and MIW products are built in 4'' wide modules, while MIV and MIR products are built in 2'' wide modules.
These modules can be plugged into an M050 half 19'' rack case or an M100 full 19'' rack case. M050 cases can
hold a maximum of 8'' in total module length (i.e. 2 MIF modules or 1 MIF and 2 MIV modules), while the M100 case
can hold a maximum of 16'' in total module length (i.e. 4 MIFs, 2 MIF and 4 MIVs, or 8 MIV modules). A system
comprised of several M family relays in the same case is called an M+ System.
The information required to completely specify the relay is provided in the following table:
MIF
-
-
P
A
I
*
OPTION 1: Configurable I/O, Event recording, oscillography
OPTION 2: Includes all OPTION 1 features, plus Cold load pickup, breaker failure to open protection, breaker
health, configurable Logic.
GEK-106273L
PRODUCT DESCRIPTION
Table 2.2: - ORDER CODES
-
-
-
-
0
0
1
5
1
5
N
L
E
F
0
1
2
MIF Digital Feeder Protection
-
*
*
-
DESCRIPTION
3 Phase + Ground
ANSI Curves
IEC Curves
Phases:
CT In = 1A (0.1-2.4 A)
CT In = 5A (0.5-12 A)
Ground:
CT In = 1A (0.1-2.4 A)
CT In = 5A (0.5-12 A)
Sensitive ground In = 1 A
(0.005-0.12 A)
Very sensitive ground. In = 1 A
(0.002-0.048 A)
Language:
English
French
No options, basic unit
Option 1(*)
Option 2 (*)
Power Supply:
F
24-48 Vdc (Range: 19~58 Vdc)
H
110-250 Vdc (Range: 88~300 Vdc)
110-230 Vac (Range: 88~264 Vac)
0
0
Standard model
0
5
Special model with configuration
for 1 shot recloser
(Only OPTION 2 models)
Individual relay
C
S
Mounted in a M+ System **
2-15