Phase / Ground Ioc Settings (50Ph / 50Pl / 50Nh / 50Nl) (Table 2) - GE GEK-106273L Instruction Manual

Digital feeder protection
Table of Contents

Advertisement

5.3.3.
Ph IOC High Set Table
2
50PH Permission to Trip
50PH Tap / Pickup
50PH Time Delay
Ph IOC Low Set Table 2
50PL Permission to Trip
50PL Tap / Pickup
50PL Time Delay
Gnd IOC High Set Table
2
50NH Permission to Trip
50NH Tap / Pickup (1/5 A
ground)
50NH Tap / Pickup Value
(sensitive ground)
50NH Time Delay
Gnd IOC Low Set Table
2
50NL Permission to Trip
50NL Tap / Pickup (1/5 A
ground)
50NL Tap / Pickup Value
(sensitive ground)
50NL Time Delay
GEK-106273L
PRODUCT DESCRIPTION

PHASE / GROUND IOC SETTINGS (50PH / 50PL / 50NH / 50NL) (TABLE 2)

ENERVISTA MII
SETUP
50PH Function (Table
2)
50PH Trip Permission
T2
50PH Pickup T2
50PH Time Delay T2
50PL Function (Table
2)
50PL Trip Permission
T2
50PL Pickup T2
50PL Time Delay T2
50NH Function (Table
2)
50NH Trip Permission
T2
50NH Pickup T2
50NH Pickup T2
50NH Time Delay T2
50NL Function (Table
2)
50NL Trip Permission
T2
50NL Pickup T2
50NL Pickup T2
50NL Time Delay T2
MIF Digital Feeder Protection
HMI
DEFAULT
F50PH T2
TRIP 50PH
No
T2
TAP 50PH T2 1 In (Phase)
TIME 50PH
0 s.
T2
F50PL T2
TRIP 50PL T2
No
TAP 50PL T2 1 In (Phase)
TIME 50PL
0 s.
T2
F50NH T2
TRIP 50NH
No
T2
1 In
TAP 50NH T2
(Ground)
TAP 50NH T2
0.005 A
TIME 50NH
0 s.
T2
F50NL T2
TRIP 50NL
No
T2
1 In
TAP 50NL T2
(Ground)
TAP 50NL T2
0.005 A
TIME 50NL
0 s.
T2
RANGE
STEP
Y/N
NA
0.1 – 30 In (Ph)
0.1 In (Ph)
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 30 In (Ph)
0.1 In (Ph)
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 30 In
0.1 In (G)
(Gnd)
0.005-0.12 A
0.001 A
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 30 In
0.1 In (G)
(Gnd)
0.005-0.12 A
0.001 A
0 – 600.00 s.
0.01 s.
5-33