Phase / Ground Ioc Settings (50Ph / 50Pl / 50Nh / 50Nl) - GE GEK-106273L Instruction Manual

Digital feeder protection
Table of Contents

Advertisement

Phase
IOC
High
Setting
50PH
Permission
to
Trip
50PH Tap / Pickup
50PH Time Delay
Phase IOC Low Setting
50PL
Permission
to
Trip
50PL Tap / Pickup
50PL Time Delay
Ground IOC High Set.
50NH
Permission
to
Trip
50NH Tap / Pickup (for
1/5 A ground)
50NH Tap / Pickup (for
sensitive ground)
50NH Time Delay
Ground
IOC
Low
Setting
50NL
Permission
to
Trip
50NL Tap / Pickup (for
1/5 A ground)
50NL Tap / Pickup (for
sensitive ground)
50NL Time Delay
5-30
5.2.3.
ENERVISTA MII
SETUP
50PH Function
50PH Trip Permission
50PH Pickup
50PH Time Delay
50PL Function
50PL Trip Permission
50PL Pickup
50PL Time Delay
50NH Function
50NH Trip Permission
50NH Pickup
50NH Pickup
50NH Time Delay
50NL Function
50NL Trip Permission
50NL Pickup
50NL Pickup
50NL Time Delay
MIF Digital Feeder Protection
SETTINGS

PHASE / GROUND IOC SETTINGS (50PH / 50PL / 50NH / 50NL)

HMI
DEFAULT
F50PH
TRIP 50PH
No
TAP 50PH
1 In (Phase)
TIME 50PH
0 s.
F50PL
TRIP 50PL
No
TAP 50PL
1 In (Phase)
TIME 50PL
0 s.
F50NH
TRIP 50NH
No
TAP 50NH
1 In (Ground) 0.1 – 30 In (Gnd)
TAP 50NH
0.005 A
TIME 50NH
0 s.
F50NL
TRIP 50NL
No
TAP 50NL
1 In (Ground) 0.1 – 30 In (Gnd)
TAP 50NL
0.005 A
TIME 50NL
0 s.
RANGE
STEP
Y/N
NA
0.1 – 30 In (Ph)
0.1 In (Ph)
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 30 In (Ph)
0.1 In (Ph)
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 In (G)
0.005-0.12 A
0.001 A
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 In (G)
0.005-0.12 A
0.001 A
0 – 600.00 s.
0.01 s.
GEK-106273L