7. LOGIC CONFIGURATION (ONLY OPTION 2 MODELS)

Using the ENERVISTA MII SETUP software, we can configure 4 different logics.
The default logic configuration is the following:
LOGIC
1
2
3
4
Logic functions are divided in several groups, besides Not defined function. We can configure up to eight signals in
the same Logic box with the following structure:
S1
S2
1
S3
S4
S5
2
S6
S7
3
S8
Each signal (S1...S8) has the same structure as the outputs/LEDs.
To configure a logic box, we can proceed in the same way as for the outputs/LEDs configuration per signal.
There are two timers, pickup and dropout timers, that can be assigned to each logic box.
IMPORTANT NOTE
Signals must be used in order, starting with S1. If we wish to use more than one signal in the same AND, use
S2 first and then S3. If we wish to use another AND use AND 2 first, and then AND 3.
GEK-106273L
LOGIC CONFIGURATION
CONFIGURATION
S1 = Not defined
S1 = Not defined
S1 = Not defined
S1 = Not defined
MIF Digital Feeder Protection
7.1.1.
PICKUP TIMER
DROPOUT TIMER
0
0
0
0
T
T

LOGIC DESCRIPTION

0
0
0
0
7-1