The MIF system complies with the following standards, which include the standards required by Community Directive
89/336 for the CE marking, in line with European standards. It also complies with the European directive
requirements for low voltage, and the environmental and operating requirements established in ANSI standards
C37.90, IEC 255-5, IEC 255-6 and IEC 68.
The MIF is also UL and CSA certified.
Test
Insulation Test Voltage:
Surge Test Voltage:
1 MHz Interference:
Electrostatic Discharge:
Radiointerference:
Radiated Electromagnetic fields with
amplitude modulation.
Radiated Electromagnetic fields with
amplitude modulation. Common mode.
Radiated Electromagnetic fields with
frequency modulation.
Fast Transients:
Magnetic fields at industrial frequency:
Power Supply interruptions:
Temperature:
RF Emission:
Sinusoidal Vibration:
Shock:
Insulation Test:
GEK-106273L
PRODUCT DESCRIPTION
2.13.8.
Standard
IEC 60255-5
IEC 60255-5
IEC 60255-22-1
IEC 60255-22-2
EN 61000-4-2
IEC 60255-22-3: 40 MHz, 151 MHz,
450 MHz and cellular phone.
ENV 50140
ENV 50141
ENV 50204
ANSI/IEEE C37.90.1
IEC 60255-22-4
BS EN 61000-4-4
EN 61000-4-8
IEC 60255-11
IEC 57 (CO) 22
EN 55011
IEC 60255-21-1
IEC 60255-21-2
IEC255-5 (Tested on CTs, Power Supply terminals, Contact
Inputs and Contact Outputs)
MIF Digital Feeder Protection
TYPE TESTS & CERTIFICATIONS
Class
2kV, 50/60 Hz 1 min
5 kV, 0.5 J. (3
positive pulses and 3
negative.)
III
IV
8 kV in contact,
15 kV through air.
III
10 V/m
10 V/m
10 V/m
IV
IV
IV
30 AV/m
B
II
I
2.13.9.

PRODUCTION TESTS

2-21