It is possible to change by hardware the contact configuration from normally open to normally closed (see the first
point of this document).
OUT1 normally closed and OUT2 normally open:
o
The hardware configuration corresponds to OUT1 NC and OUT2 NO. To operate with this hardware
configuration it is necessary to configure by software the OUT1 as NOT ASIGNED, so it never
change its state and remains closed, and OUT2 as required by the application (output configuration is
only available in models option 1 and 2).
OUT1 normally open and OUT2 normally closed:
o
The hardware configuration corresponds to OUT1 NO and OUT2 NC. To operate with this hardware
configuration it is necessary to configure by software the OUT2 as NOT ASIGNED, so it never
change its state and remains closed, and OUT1 as required by the application (output configuration is
only available in models option 1 and 2).
GEK-106273L
PRODUCT DESCRIPTION
MIF Digital Feeder Protection
3-35