6: History; View Events - Honeywell Fire-Lite Alarms MS-5UD Series Manual

Fire alarm control panels
Table of Contents

Advertisement

Programming
DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Onboard DACT Screen #2
3.5.6 History
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
HISTORY

1=VIEW EVENTS

2=ERASE HISTORY
History Screen
102
will return to the Service Terminal screen.
Supervised Phone Line
The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2 by
the DACT when using an alternate means of secondary transmission path. The factory default set-
ting is Phone Line 2 supervised.
Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the following
screen to be displayed:
SUPERVISE PHONE LINE
1=PHONE LINE 2
Each press of the 1 key while viewing this screen will toggle the option between Supervise Phone
Line 2 Yes and No.
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 3 while viewing Programming Screen #2 will display the History options
as shown in the following display:
1=VIEW EVENTS
2=ERASE HISTORY
View Events
Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as
illustrated in the following:
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
YES
HISTORY
History Screen
HISTORY
View Events Screen
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Master Programming Level