ANN-BUS Devices

Powering ANN-BUS Devices from Auxiliary Power Supply

Figure 2.21 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as
the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANN-BUS
power requirements.
FCPS-24FS6/8
2.8.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS" on page 82).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
NOTE: address (ID Number) DIP switches on some devices may have more than 5 switch
positions. Unless otherwise specified in the documentation supplied with each device, switch
positions 6 and above must be set to OFF.
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
TB3
-24 VDC
+24 VDC
Figure 2.21 Powering ANN-BUS Devices from FCPS-24FS6/8
Address
Switch 5
not valid
OFF
OFF
01
OFF
OFF
02
OFF
OFF
03
OFF
OFF
MS-5UD/MS-10UD
ANN-BUS
ANN-BUS and power wiring are
supervised and power-limited
Switch 4
Switch 3
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
Installation
ANN-80
Switch 2
Switch 1
OFF
ON
OFF
ON