Master Programming Level
TIMER
1=PAS DELAY
120
2=PRE SIGNAL
120
3=WATERFLW DELAY
0
Timer Screen #1
TIMER
1=AC LOSS DELAY 2
Timer Screen #2
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.
Note that the FACP can have both PAS and Pre-signal timers programmed with values but a zone
can only use either the PAS or Pre-signal feature, but not both.
Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:
RANGE 00-90 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.
AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length
of the desired delay. Press 1 while viewing Timer Screen #2 to display the following:
AC LOSS DELAY
RANGE 00-24 HOURS
A flashing cursor will appear in the lower left corner of the display. The factory default setting is
02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When the sec-
ond digit is entered, the display will return to AC Loss Delay Screen #1.
NOTE: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC Loss
exist in the panel, the System Trouble relay will delay activation for the duration of the AC Loss
Delay setting.
WATERFLOW DELAY
Waterflow Delay Screen
AC Loss Delay Screen #1
Programming
77