Installation

2.6 Digital Communicator

Two independent telephone lines can be connected to the control panel. Telephone line con-
trol/command is made possible via double line seizure as well as usage of an RJ31X style intercon-
nection. Note that it is critical that the panel's digital communicator be located as the first device
on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
Network
RJ31X
Service
Provider's
Facilities
Telephone
Line
Network
Demarcation
Point
The control panel's digital communicator is built into the main circuit board. Connection and wir-
ing of two phone lines is required as shown below.
Primary
Secondary
phone line
phone line
active LED
active LED
J8
Male plug
connectors
36
Customer Premises Equipment and Wiring
Jack
FACP with DACT
Telephone
Answering
System
Figure 2.12 DACT Installation
Tip
Ring
Secondary
phone line PH-2
J9
Modular female
connectors
Figure 2.13 Wiring Phone Jacks
Unused
RJ-11 Jack
Fax Machine
Telephone
(Secondary Lines)
Incoming Telco
phone lines
Green Wire
Ring
to premise phones
Red Wire
Tip
1 2 3 4 5 6
7
8
RJ31X
Jack
Note: Shorting bars
inside RJ31X Jack
removed during
male plug insertion
7 foot cable
MCBL-7
(ordered separately)
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Digital Communicator
Computer
Telephone
Unused
J-11 Jack
(Primary Lines)
Incoming Telco
Tip Green Wire
phone lines
Red Wire
Ring
Ring
to premise phones
Tip
1 2 3 4 5 6 7
8
RJ31X
Jack
Primary
phone line
PH-1