Honeywell Fire-Lite Alarms MS-5UD Series Manual page 19

Fire alarm control panels
Table of Contents

Advertisement

Specifications
The following figure illustrates the maximum current that is possible for each major panel output
circuit and the total current available from the FACP with the FLPS-7 power supply. This applies
to the MS-5UD-7, MS-5UD-7C, MS-10UD-7, MS-10UD-7C, MS-5UD-7E, and MS-10UD-7E.
TB9
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable Power
TB5
NAC #1
NAC #2
TB7
NAC #3
NAC #4
TB3
Primary
ANN-BUS
TB1
ANN-SEC
Option Card
Refer to the battery calculations section for additional information.
Figure 1.2 Current Availability with FACP and FLPS-7 Power Supply
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
0.5 amp max
per circuit
0.5 amp max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
0.5 amp max
per circuit
0.5 amp max
per circuit
Standby
1.0 amp max
per panel
Standby
1.0 amp max
per panel
Product Description
Alarm
7.0 amps
max
per panel
19