Honeywell Fire-Lite Alarms MS-5UD Series Manual page 137

Fire alarm control panels
Table of Contents

Advertisement

Calculating the System Current Draw
Table 7.3 contains three columns for calculating current draws. For maximum output current avail-
ability per circuit and per panel, refer to Section 1.2, "Specifications", on page 15. For each col-
umn, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy
the totals from Calculation Column 2 and Calculation Column 3 to Table 7.4 on page 138.
Calculation Column 1
Device Type
Primary, Non-Fire Alarm Current
Qty
Main Circuit
Board
MS-5UD
or
1
MS-10UD
CAC-5X
[
]
4XTMF
[
]
1 max.
ANN-SEC card
[
]
1 max.
ANN-80(C)
[
]
ANN-I/O
[
]
ANN-RLY
[
]
3
ANN-(R)LED
[
]
ANN-S/PG
[
]
2-wire Detector
[
]
Heads
4-wire Detector
[
]
Heads
Power
[
]
Supervision
6
Relays
NAC #1
NAC #2
NAC #3
NAC #4
Current Draw
from TB9
(nonalarm)
Sum each
7
Primary Non-Alarm =
column
for
totals
1 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
2 The current draw shown represents one zone (IDC) on the main circuit board in alarm. One zone consumes
0.040 amps.
3 An ANN-LED is supplied standard with the MS-5UDC and MS-10UDC.
4 Refer to the Device Compatibility Document for standby current.
5 Enter the number of IDCs used minus one.
6 Must use compatible listed Power Supervision Relay.
7 Total current draw listed above cannot exceed 3.25 amps for the MS-5UD-3(E), 3.28 for the MS-10UD-3(E),
7.25 for the MS-5UD-7(C/E), and 7.28 for the MS-10UD-7(C/E).
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Secondary, Fire Alarm Current
(amps)
X[current
Total
Qty
draw]=
X[0.110]=
1
X[0.133]=
X[0.001]=
[
X[0.005]=
[
1 max.
X[0.003]=
[
1 max.
X[0.037]=
[
X[0.035]=
[
X[0.015]=
[
X[0.028]=
[
X[0.045]=
[
4
X[
]
=
[
4
X[
]
=
[
X[0.025]=
[
[
[
[
]=
Table 7.3 System Current Draw Calculations
Calculation Column 2
(amps)
X [current draw]
Total
=
1, 2
X[0.214]
=
1, 2
X[0.282]
=
]
X[0.001]=
1
]
X[0.011]
=
]
X[0.003]=
]
X[0.040]=
]
X[0.200]=
]
X[0.075]=
]
X[0.068]=
]
X[0.045]=
5
]
X[0.040]=
5
]
X[0.040]=
]
X[0.025]=
]
X[
]=
]
X[
]=
[
]=
Secondary Alarm =
Power Supply Calculations
Calculation Column 3
Secondary, Non-Fire Alarm
Current
(amps)
X[current
Qty
Total
draw]=
X[0.110]=
1
X[0.133]=
[
]
X[0.001]=
[
]
X[0.005]=
1 max.
[
]
X[0.003]=
1 max.
[
]
X[0.015]=
[
]
X[0.035]=
[
]
X[0.015]=
[
]
X[0.028]=
[
]
X[0.045]=
4
[
]
X[
]
=
4
[
]
X[
]
=
[
]
X[0.025]=
[
]=
Secondary Non-Alarm =