Honeywell BC-200 Operation, Installation & Programming Manual page 99

Table of Contents

Advertisement

Appendix
9.3.2.3
E
VENT
Switch 1 of DIP switch SW1 will enable the buzzer for alarms.
Switch 2 of DIP switch SW1 will enable the buzzer for faults.
Switch 7 of DIP switch SW1 will enable the RS232 port on the LCD80 for programming.
(Note: Activation of this switch prevents the LCD80 from communicating with the FIP.)
Switch 8 of DIP switch SW1 will select terminal mode (OFF) or annunciator mode (ON)
If the buzzer is enabled, pressing the "MUTE" button will silence the buzzer until a new event is received.
9.3.2.4
D
ISPLAY
The LCD Display is made up of 4 lines of 20 characters each. Events are displayed as:
Line 1
Line 2
Line 3
Comms Indicator
In the above example, the FIP has activated Point 6 on the LCD80. It is the first of 5 points which are active. The
Comms Indicator "Spins" when messages are being received by the LCD80.
EAST WING
SOUTH
CORRIDOR
* Pt 12 Msg 1 of 1
9.3.2.5
S
PECIAL
NO ACTIVE POINTS
COMMS FAILURE
BC-200 Manual – P/N DOC-01-013
S
OUNDER
EAST WING
NORTH
CORRIDOR
* Pt 6 Msg 1 of 5
Point
Message
Number
Number
In this example: The FIP has activated Point 12 on the LCD80.
It is the only point active.
M
ESSAGES
There are no active points on the panel programmed to
display on the LCD-80.
This messages flashes: The LCD80 has not been polled by
the CPU in over 10 seconds
Total Messages
99