7.3.6.13 S
ERVICE
Selecting 'Walk' will take you to the 'Walk Test Output Target List' where you can select an output for the Walk
Test. (Note: This output will activate for approximately 2 seconds whenever a device is tested during the walk
test). Throughout the duration of the Walk Test, the 'FAULT', 'EXT BELL ISOLATE' and "WARNING SYSTEM
ISOLATE" front panel LEDs will pulse on and off. This screen will appear as follows:
WALK TEST OUTPUT TARGET LIST
DAY MODE
20 JULY 2002 14:44:37
SELECT AN OUTPUT FOR WALK TEST:
00.004.01
BELL OUTPUT
00.004.O2
WARNING SYSTEM
00.004.O3
(LOCAL RELAY)
00.004.O4
(LOCAL RELAY)
00.004.O5
GENERAL ALARM OUTPUT
00.004.O6
COMMON FAULT OUTPUT
00.004.O7
(LOCAL RELAY)
00.004.08
(LOCAL RELAY)
XR1
(EXPANSION RELAY)
XR2
(EXPANSION RELAY)
XR3
(EXPANSION RELAY)
XR4
(EXPANSION RELAY)
XR5
(EXPANSION RELAY)
XR6
(EXPANSION RELAY)
XR7
(EXPANSION RELAY)
XR8
(EXPANSION RELAY)
UP
DOWN
After selecting the walk test output, the following screen will appear. You must then select the Group Zone or
Loop you wish to test.
WALK TEST
DAY MODE
20 JULY 2002 14:44:37
PERFORM WALK TEST ON:
1) ZONE ...... SELECT A GROUP ZONE
2) LOOP ...... SELECT AN ANALOGUE LOOP
UP
DOWN
After selecting either a group zone or loop, you are taken to the respective group zone or loop walk test screen
showing all the input points in the zone or loop that can be "walk tested". From this screen, you are able to
remove individual devices from the walk test if you wish, or simply start the walk test by pressing the START
button.
BC-200 Manual – P/N DOC-01-013
M
– T
– W
ENU
EST
A = 0
F = 0
I = 1
N = 0
SELECT
BACK
A = 0
F = 0
I = 1
N = 0
SELECT
BACK
ALK
Actions:
Use the UP and DOWN buttons to select the
appropriate point and then press the SELECT
button to select the output point.
Actions:
Use the UP and DOWN buttons to select the
appropriate menu item and then press the
SELECT button to select either a group zone or
an Analog loop to be walk tested.